3. Disconnect the overload fixing and connecting
screws from the bottom of the contactor.
4. Ensure that any replacement overload is of the
correct rating and that it is reset correctly. See
Page 41, Section 10.1.6.
15.3 Control Circuit Protection
The control circuit only is protected by a 10 Amp re-
settable circuit breaker and does not disconnect the
mains electrical supply to this appliance.
NOTE: In off position, the circuit breaker will still
have live electrical components exposed.
15.4 Combination Fan/Limit Thermostat
To gain access to the thermostat:
1. Loosen the cover retaining screw (on top) and
remove cover.
2. Disconnect the electrical connections by push-
ing in with a small screwdriver and pulling out
the wiring. See Page 65, Figure 24.
3. Unscrew the conduit bush and the two screws
and withdraw the unit from the cabinet.
4. Reverse these instructions to refit. See Page
41, Figure 17 to set the new thermostat.
15.5 Main Fan Motor (3 Ø Belt Drive)
1. Disconnect electrical connections at contactor
and overloads. See Page 63, Section 15.2.
2. For Star/Delta starters, there are six wires
between the motor and the starter.
3. Remove the left lower side panel to access the
motor.
4. Unscrew the bolts securing the motor to the
mounting bracket. Lift the motor out.
5. Reverse these instructions to refit, tensioning
the belts as on Page 52, Figure 23 and ensur-
ing the pulleys are aligned.
6. For Star/Delta starters, pay specific attention to
the six motor connections.
15.6 Main Fan Units
Depending on the model of the heater, the main fan
unit will be direct drive (with integral motor) or belt
drive. Models 060-100 are belt drive, double fan
units. All the fans are secured to the base of the
heater by four bolts per fan case, and to the fan tray
by bolts through the outlet flange.
To gain access to the fans:
1. R e m o ve the lower side panels of the heater.
For models 060-100 and High Flow models,
remove the upper side panels of the same side
and the vertical centre bar to allow the fans to
slide out of the cabinet.
2. Disconnect the electrical connections. On
direct drive units, these will be at the terminal
block for single phase and at the contactor for
three phase.
3. Remove the screws. The fan will pull o
ut of the
heater through the side.
4. Reverse these instructions to refit, tensioning
the belts as on Page 52, Figure 23.
5. Check the correct rotation of the fan as on
Page 41, Section 10.1.5.
NOTE: The direct drive fan unit motor can only be
replaced as a complete fan/motor assembly.