SECTION 3: CRITICAL CONSIDERATIONS
7 of 85
3.6 Electrical Supply
A permanent 230 V, 50 Hz, 1 Ø is required on
models 15 to 30 and 400 V, 50 Hz, 3 Ø and neutral
required on models 40 to 100 (special version MGB
and MOB 040 and 050 models are available as belt
drive). The heater also requires suitable energy
controls in accordance with Page 27, Section 9.
ON/OFF control, temperature control, time control,
and frost protection are available as a remote
control, which needs to be site wired for proper
operation of the heater. Alternatively, any remote
energy controls may be used which must be wired in
accordance with Page 28, Section 9.3 through Page
39, Section 9.14.
3.7 Flue
Choose heater siting to allow for the proper location
of the flue. Each heater must be fitted with an
individual and correctly sized sealed flue system.
See Page 17, Section 6.
No other appliance may be connected to the flue.
For room sealed installation, the air intake must be
the same size sealed system and the flue/air intake
must terminate at an approved concentric wall or
roof terminal.
DANGER
Electrical Shock Hazard
Disconnect electric before service.
Heater must be properly grounded.
Failure to follow these instructions can result
in death or electrical shock.