COMBAT
®
CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL
8 of 85
SECTION 4: SPECIFICATIONS
4.1 MGB & MOB Internal Heaters
Dimension Data - MGB & MOB Internal Heaters
NOTES: Horizontal cabinet heaters are designed to lie on their left side as standard.
For vertical models, add 54 mm (2 in) to the right side of the cabinet for the fan/limit thermostat.
For horizontal models, add 54 mm (2 in) to the top of the cabinet for the fan/limit thermostat.
*All MOB heaters must be connected to a suitable flue constructed of single wall stainless steel.
*MGB 15-50 heaters must be connected to a suitable flue constructed of single wall aluminium or stainless steel.
** Maximum flue length between heater and flue terminal (horizontal only).
Front View
(all models)
Side View
(Models 015 - 050)
Rear View
(all models)
Side View
(Models 060 - 0100)
Model 015/020 030 040 050 060/070/080 0100
A
Width
mm
(in)
723
28.5
723
28.5
853
33.6
857
33.7
1016
40
1016
40
B
Depth, Cabinet Only
mm
(in)
860
33.9
860
33.9
860
33.9
1015
40
1676
66
1994
79
C
Height, Cabinet Only
mm
(in)
1778
70
1778
70
1956
77
1956
77
1956
77
1956
77
D
Depth, Overall
mm
(in)
1267
50
1267
50
1337
53
1496
59
2156
85
2496
98
E
Height, Including Heads
mm
(in)
2007
79
2083
82
2261
89
2261
89
2261
89
2261
89
F
Left/Right Air Inlet Spigot - Depth
mm
(in)
781
31
781
31
781
31
940
37
1600
63
1918
76
G
Left/Right Air Inlet Spigot - Height
mm
(in)
457
18
457
18
560
22
560
22
560
22
559
22
H
Rear Air Inlet Spigot - Depth
mm
(in)
648
26
648
26
781
31
781
31
NA NA
J
Rear Air Inlet Spigot - Height
mm
(in)
361
14
361
14
446
18
446
18
NA NA
Flue Diameter*
mm
(in)
100
4
130
5
130
5
130
5
229
9
229
9
Flue Length**
m
(ft)
8
27
8
27
8
27
8
27
NA NA
Weight
kg
(lbs)
200
441
200
441
245
541
270
596
440
970
530
1170
Comentarios a estos manuales