COMBAT
®
CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL
52 of 85
3. For oil-fired burners it is recommended that the
atomising oil nozzle be replaced during the
annual service.
12.3 Fan/Motor Assembly Maintenance (all
models)
The main fan bearings are permanently sealed and
do not need lubrication. Before cleaning, turn off fuel
and electrical supply. Remove the heater side
panels and use a small brush or duster to clean the
fan blades from each side. Replace panels when
done.
Figure 23: Belt Tension
Check the condition and tension of the drive belts.
The condition is best inspected with the belts
removed. Check for chaffing or lateral cracks.
Replace belts as a matched pair as necessary.
Do not over-tighten belts, as this may cause bearing
damage.
12.4 Heat Exchanger Maintenance
Ensure that the front collector box is clean and that
the turbulators fitted to the tubes are in good
condition.
Also inspect the joint between the heat exchanger
and the flue to ensure that it is still sealed.
1. If maintenance is needed, remove the burner.
See Page 63, Section 15.1.
2. Remove the upper front panel.
3. Remove the front cover of the heat exchanger.
4. Remove and inspect the turbulators.
5. Clean out any deposits from flue ways and the
combustion chamber, using a vacuum cleaner
and brush. Inspect the combustion chamber
and heat exchanger for damage or corrosion.
6. Any damage must be referred to
Roberts-Gordon Europe Limited.
7. Replace components in reverse order to above
- replacing gasket material and any damaged
turbulators.
8. Inspect and repair any damage to the seal
between the flue and the flue spigot.
12.5 Thermal Insulation
While the upper panels are removed for heat
exchanger servicing, the thermal insulation fitted to
all the upper panels must be inspected. Insulation
should be sound, with the foil face in good condition.
If any thermal insulation is in poor condition, then it
must be replaced with new insulation material and
suitably sealed at the edges with adhesive foil tape.
Motor
Pulley
Fan
Pulley
8 mm to 10 mm
Comentarios a estos manuales