SECTION 8: FUEL PIPE WORK
25 of 85
system, the pump draws fuel from the tank, then
pushes it through the installation under pressure.
The pressure is controlled at the pump by a
pressure relief valve at approximately 0.8 BAR (12
psi). When a pressurised system is used, a pressure
reducing valve set at approximately 0.3 BAR (5 psi)
should be installed on the fuel inlet to each heater
after the manual isolating valve. This protects the oil
pump from the danger of possible over pressure
under fault conditions.
The electrical supply for the pump installation will
depend upon the type of pumps chosen, but will
normally be set to run continuously.
Figure 15: B. M. Oil Lifter