SECTION 4: SPECIFICATIONS
13 of 85
4.7 Technical Data - Ecoflam Oil-Fired Burners
NOTE: For adjustment of head setting, see Ecoflam Instructions.
* Nozzle sizes are quoted in US gal/h. Fuel consumption is quoted in imperial gal/h.
Model
015 020 030 040 050 060 070 080 0100
Gross Heat Input
(kW)
(Btu/h) x (1000)
55.5
189.4
73.3
250.1
93.2
318.0
129.9
443.2
162.0
552.7
208.0
709.7
242.0
825.7
275.2
939.0
348.5
1189.1
Heat Output
(kW)
(Btu/h) x (1000)
47.4
161.8
61.2
208.9
78.4
267.4
110.2
375.9
134.5
458.8
177.7
606.5
205.3
700.3
230.4
786.2
293.4
1001.0
Burner Type MAX 8 MAX 8 MAX 12 MAX 15 MAX 15 MAX 20 MAX 20 MAX 30 MAX 35
Oil Pump Connections (in) 3/8
Light Fuel Oil (Gas Oil) Data
Nozzle Size *US (gal/h) 1.1 1.35 1.75 2.25 3 4.5 5 5.5 2.5
Angle & Type 60°H 60°B
60°S 60°B 60°B
Make Danfoss
Head Setting (number) 0 1 0.5 0 0 1.5 1.5 1.5 1.5
Air Setting (number) .45 (1/2) 1.4 4 2 2.5 2.3 3 4.5 3
Burner Fuel Pressure
(Bar)
(lbf/in
2
)
10.6
154
13
189
12.5
181
15.5
225
14
203
11
160
10.3
149
10.3
149
12
174
Fuel Consumption
(L/h)
*UK (gal/h)
5.3
1.17
7.0
1.55
8.9
1.96
12.4
2.73
15.6
3.43
20.0
4.4
23.2
5.1
26.4
5.8
30.56
6.72
Maximum Oil Pressure to
Pump Inlet
(Bar)
(lbf/in
2
)
2
2.9
Kerosene Data
Nozzle Size *US (gal/h) 1.25 1.65 2.25 3 3.5 5 5.5 6 5.5
Angle & Type 60°EH
60°B 60°ES 60°B
60°B
Make Danfoss
Head Setting (number) 0 1 0.5 0
0 1.5 1.5 1.5
1.5
Air Setting (number) .45 (1/2) 1.4 4 2 2.5 2.3 3 4.5 3
Burner Fuel Pressure
(Bar)
(lbf/in
2
)
8.6
125
9
131
8.1
117
9.5
138
7 / 10
102 / 145
9.5
138
8.5
123
9.5
138
8.5
123
Fuel Consumption
(L/h)
*UK (gal/h)
5.5
1.2
7.2
1.6
9.2
2.0
12.8
2.8
16.1
3.5
20.6
4.5
23.9
5.3
27.2
6.0
31.5
6.9